The tank's counterpart of get_storage_level(): the level in kWh thermal at
the start of each slot, starting from init, with
S[t+1] = max(k * S[t] + (cop[t] * power[t] + backup[t] - heat_demand[t]) * dt, 0) and k = (1 - loss/100)^dt, dt being the time resolution in
hours. Level 0 is the inlet temperature: an empty tank gives no more heat,
and the demand it cannot serve is unmet heat.
Arguments
- power
numeric vector, compressor electric power (kW), such as the result of
add_tank_optimization()- heat_demand
numeric vector, heat demand (kW thermal)
- cop
numeric vector, coefficient of performance (heat per electric kWh)
- init
numeric, level before the first slot (in kWh, not %)
- loss
numeric, standing loss of the level (% per hour)
- time_resolution
numeric, time resolution of the time-series (in minutes)
- backup
numeric, backup heater power (kW electric = kW thermal):
attr(result, "backup_kw")ofadd_tank_optimization(), or 0 without a backup heater